GlobalRoof Thermo-Acoustic IN 226 | IN 227


Parallel to main tray - non-structural trays
(can also be considered perpendicular way)

Advantages: Aesthetic
No visible fixings for the insulation on behind façade facing

It is requested to add a complementary insulation to fill the air gap between the panels
GlobalRoof Thermo-Acoustic IN 226
1. Tray HACIERCO C 1,00mm thick (under condition of structural verification)
2. Vapour barrier
3. Purlin Cleat or spacer (see guide)
4. Mineral wool 60mm thick (Isover)
5. Purlin to obtain 230mm thick between Tray and Profile (1 and 7) (see guide)
6. Feutral cladding 80mm thick(Isover)
7. Profile: Fréquence, Océane, Trapéza 1,00mm thick (under condition of structural verification)
 
The installation should be carried out according to good practice: NF DTU 40.35 -  in accordance with the local professionals rules
 
Width at load bearing supports for Trays HACIERCO C: 100mm minimum
 

GlobalRoof Thermo-Acoustic IN 227
1. Tray HACIERCO C 1,25mm thick (under condition of structural verification)
2. Vapour barrier
3. Purlin Cleat or spacer (see guide)
4. Mineral wool 200mm thick minimum: 100 kg/m3
5. Mineral wool 200mm thick minimum: 100 kg/m3
6. Purlin to obtein 275mm thick between Tray and Profile (1 and 7)(see guide)
7. Profile: Hacierco 1,25 mm thick (under condition of structural verification)
 
The installation should be carried out according to good practice: NF DTU 40.35 -  in accordance with the local professionals rules
 
Width at load bearing supports for Trays HACIERCO C: 100mm minimum
 